Name/Model: |
Closed-loop Hall current sensor CHB-40KA, 50KA |
Rated input Parameter: |
DC, AC or pulsed 40KA, 50KA current / Split core |
|
SENSOR MODULE CHB-40KA, 50KA |
The SENSOR Module CHB-40KA, 50KA is a closed loop Hall current sensor to measure 40KA, 50KA DC, AC |
or pulsed currents with a galvanic isolation between the primary and secondary circuits. |
|
Closed-loop Hall Current Sensor: |
Type |
Nominal current |
Output current |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
IM(mA) |
X(%) |
Vc(V) |
mm |
CHB-40KA |
40,000 |
8,000 |
±0.4% |
±36~48 |
554X554 |
CHB-50KA |
50,000 |
10,000 |
±0.4% |
±36~48 |
554X554 |
|
Specifications: |
Principle |
Closed loop Hall effect principle |
Input current |
40,000A, 50,000A(DC、AC、Pulsed current) |
Output current |
8,000mA, 10,000mA |
Turns ratio |
1:5000 |
Frequency |
DC~100KHz |
Accuracy |
±0.4% |
Response time |
<1μS |
Linearity |
<0.1% |
Supply voltage |
±36~48V(±5%) |
Consumption |
90mA+IM(Output current) |
Isolation voltage |
Between primary and secondary circuit: 10KV RMS/50Hz/1min. |
Operating temp. |
-25…+70℃ |
Mounting on |
Fastening on panel |
Applications |
Power supplies, converters, industry auto-control, rectifiers systems etc. |
>>Back |
|
|
|
|