SENSOR MODULE CHV-25P/50~600, CHV-50P/100~1000 |
The SENSOR Module CHV-25P/*, CHV-50P/* is a closed loop Hall voltage sensor to measure 50V…1000V DC, |
AC or pulsed voltages with a galvanic isolation between the primary and secondary circuits. |
|
Closed-loop Hall Voltage Sensor: Output 5V |
Type |
Nominal voltage |
Output voltage |
Accuracy |
Supply voltage |
Connection |
VN(V) |
VM(V) |
X(%) |
Vc(V) |
Input |
CHV-25P/50 |
50 |
5 |
±1.0% |
±12~15 |
Terminals |
CHV-25P/100 |
100 |
|
|
|
|
CHV-25P/400 |
400 |
|
|
|
|
CHV-25P/600 |
600 |
|
|
|
|
CHV-50P/100 |
100 |
5 |
±1.0% |
±12~15 |
Terminals |
CHV-50P/400 |
400 |
|
|
|
|
CHV-50P/800 |
800 |
|
|
|
|
CHV-50P/1000 |
1000 |
|
|
|
|
|
|
|
|
|
|
Closed-loop Hall Voltage Sensor: Output 25mA |
Type |
Nominal voltage |
Output current |
Accuracy |
Supply voltage |
Connection |
VN(V) |
IM(mA) |
X(%) |
Vc(V) |
Input |
CHV-25P/50A |
50 |
25 |
±1.0% |
±12~15 |
Terminals |
CHV-25P/100A |
100 |
|
|
|
|
CHV-25P/400A |
400 |
|
|
|
|
CHV-25P/600A |
600 |
|
|
|
|
CHV-50P/100A |
100 |
25 |
±1.0% |
±12~15 |
Terminals |
CHV-50P/400A |
400 |
|
|
|
|
CHV-50P/800A |
800 |
|
|
|
|
CHV-50P/1000A |
1000 |
|
|
|
|
|
Specifications: |
Principle |
Closed loop Hall effect principle |
Input voltage |
50…1000V (DC、AC、Pulsed voltage) |
Output |
5V/25mA |
Turns ratio |
—— |
Frequency |
DC~20KHz |
Accuracy |
±1.0% |
Response time |
40μS |
Linearity |
0.2% |
Supply voltage |
±12~15V(±5%) |
Consumption |
10mA+IM(Output current) |
Isolation voltage |
Between primary and secondary circuit: 2.5KV RMS/50Hz/1min. |
Operating temp. |
-25…+70℃ |
Mounting on |
Fastening on panel |
Applications |
Power supplies, welding machines, converters, industry auto-control, motor drives, |
For industry |
electronic power system, railways, rectifiers systems etc. |
>>back |