Home > Products
 
 
  Name/Model:   AC current transducer CHY-*Y1, CHY-*Y11
  Rated input Parameter:   AC 1000A~6000A current / Split core / 50(78)x165mm

SENSOR MODULE  CHY-*Y1 (Y11)

The SENSOR Module CHY-*Y1 is a signal conditioning AC current transducer to measure 1000A…6000A AC

current with a galvanic isolation between the primary and secondary circuits.

 

Signal conditioning AC current transducer:

Type

Nominal current

Signal output

Accuracy

Supply voltage

Aperture

INA

VM / IM

X%

VcV

mm

CHY-1000Y1/#

1000

A0, A1, V0

±0.5%

+24

50x165

CHY-3000Y1/#

3000

See table 1

Split core

CHY-5000Y1/#

5000

 

Signal conditioning AC current transducer:

Type

Nominal current

Signal output

Accuracy

Supply voltage

Aperture

INA

VM / IM

X%

VcV

mm

CHY-1000Y11/#

1000

A0, A1, V0

±0.5%

+24

78x165

CHY-3000Y11/#

3000

See table 1

Split core

CHY-6000Y11/#

6000

Note: Type named, such as CHY-1000Y1/V0  Nominal input current: 0…1000A, Signal output: 0…5V

 

Table 1:

A0

A1

V0

Signal output

0…20mA

4…20mA

0…5V

DC

 

Specifications:

Input current

1000…6000A (AC current)

Signal Output

A0, A1, V0 (See table 1)

Frequency

50Hz (400Hz)

Accuracy

±0.5%

Response time

<350mS

Linearity

<0.5%

Supply voltage

+24V±5%

Consumption

30mA+IMOutput current

Isolation voltage

Between primary and secondary circuit: 5KV RMS/50Hz/1min.

Operating temp.

-25…+85

Mounting on

Fastening on panel

Applications

Power supplies, industry auto-control, motor drives, electronic power system, railways etc.

>>Back