Name/Model: |
DC voltage transducer CHZ-6KV~CHZ-15KV |
Rated input Parameter: |
DC 6KV~15KV voltage |
|
SENSOR MODULE CHZ-6KV~15KV |
The SENSOR Module CHZ-6KV~15KV is a signal conditioning DC voltage transducer to measure 6000V…15000V |
DC voltages with a galvanic isolation between the primary and secondary circuits. |
|
Signal conditioning DC voltage transducer: |
Type |
Nominal voltage |
Signal output |
Accuracy |
Supply voltage |
Connection |
VN(V) |
VM / IM |
X(%) |
Vc(V) |
Input |
CHZ-6KV/# |
6000 |
A0, A1, V0 |
±0.5% |
+24 |
Terminals |
CHZ-9KV/# |
9000 |
See table 1 |
|
|
|
CHZ-10KV/# |
10000 |
|
|
|
|
CHZ-12KV/# |
12000 |
|
|
|
|
CHZ-15KV/# |
15000 |
|
|
|
|
Note: Type named, such as CHZ-6KV/V0 Nominal input voltage: 0…6000V, Signal output: 0…5V |
|
Table 1: # |
A0 |
A1 |
V0 |
|
|
Signal output |
0…20mA |
4…20mA |
0…5V |
DC |
|
|
Specifications: |
Input voltage |
6000…15000V (DC voltage) |
Signal Output |
A0, A1, V0 (See table 1) |
Frequency |
DC |
Accuracy |
±0.5% |
Response time |
<0.35S |
Linearity |
<0.5% |
Supply voltage |
+24V(±5%) |
Consumption |
30mA+IM(Output current) |
Isolation voltage |
Between primary and secondary circuit: 15KV or 20KV RMS/50Hz/1min. |
Operating temp. |
-25…+85℃ |
Mounting on |
Fastening on panel |
Applications |
Power supplies, industry auto-control, motor drives, electronic power system, railways etc. |
>>back |
|
|
|
|