  Name/Model:   DC current transducer CHS-*AD
  Rated input Parameter:   DC 1A~10A current / DIN

SENSOR MODULE  CHS-*AD

The SENSOR Module CHS-*AD is a signal conditioning current transducer to measure 1A…10A DC current

with a galvanic isolation between the primary and secondary circuits.

 

Signal conditioning current transducer:

Type

Nominal current

Output

Accuracy

Supply voltage

Aperture

INA

VM / IM

X%

VcV

mm

CHS-1AD/#

1

A0, A1, V0

±0.5%

+24

20

CHS-2AD/#

2

See table 1

CHS-5AD/#

5

CHS-10AD/#

10

Note: Type named, such as CHS-1AD/V0  Nominal input current: 0…1A, Signal output: 0…5V

 

Table 1: #

A0

A1

V0

Signal output

0…20mA

4…20mA

0…5V

DC

 

Specifications: 

Input current

1…10A (DC)

Signal Output

A0, A1, V0 (See table 1)

Frequency

DC

Accuracy

±0.5%

Response time

<0.35S

Linearity

<0.2%

Supply voltage

+24V±5%

Consumption

60mA+IMOutput current

Isolation voltage

Between primary and secondary circuit: 2.5KV RMS/50Hz/1min.

Operating temp.

-25…+85

Fastening

35mm DIN rail

Applications

Power supplies, industry auto-control, motor drives, electronic power system, railways etc.