Name/Model: |
AC current transducer CHS-*AS |
Rated input Parameter: |
AC 1A~300A current / DIN / ¢20mm |
|
SENSOR MODULE CHS-*AS |
The SENSOR Module CHS-*AS is a signal conditioning current transducer to measure 1A…300A AC current |
with a galvanic isolation between the primary and secondary circuits. |
|
Signal conditioning current transducer: |
Type |
Nominal current |
Output |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
VM / IM |
X(%) |
Vc(V) |
mm |
CHS-1AS/# |
1 |
A0, A1, V0 |
±0.5% |
+24 |
¢20 |
CHS-10AS/# |
10 |
See table 1 |
|
|
|
CHS-50AS/# |
50 |
|
|
|
|
CHS-100AS/# |
100 |
|
|
|
|
CHS-200AS/# |
200 |
|
|
|
|
CHS-300AS/# |
300 |
|
|
|
|
Note: Type named, such as CHS-1AS/V0 Nominal input current: 0…1A, Signal output: 0…5V |
|
Table 1: # |
A0 |
A1 |
V0 |
|
|
Signal output |
0…20mA |
4…20mA |
0…5V |
DC |
|
|
Specifications: |
Input current |
1…300A (AC) |
Signal Output |
A0, A1, V0 (See table 1) |
Frequency |
50Hz (400Hz) |
Accuracy |
±0.5% |
Response time |
<0.35S |
Linearity |
<0.2% |
Supply voltage |
+24V(±5%) |
Consumption |
60mA+IM(Output current) |
Isolation voltage |
Between primary and secondary circuit: 2.5KV RMS/50Hz/1min. |
Operating temp. |
-25…+85℃ |
Fastening |
35mm DIN rail |
Applications |
Power supplies, industry auto-control, motor drives, electronic power system, railways etc. |
>>back |
|
|
|
|