Home > Products
 
 
  Name/Model:   AC current transducer of ON-OFF output CHY-*AF/K
  Rated input Parameter:   AC 1A~300A current

SENSOR MODULE  CHY-*AF/K

The SENSOR Module CHY-*AF/K is an ON-OFF output AC current transducer to measure 1A…300A AC current

with a galvanic isolation between the primary and secondary circuits.

 

ON-OFF output AC current transducer:

Type

Nominal current

Relay output

Accuracy

Supply voltage

Aperture

INA

@ Input < IN

X%

VcV

mm

CHY-1AF/K1

1

Open

±1.0%

+24

20

CHY-5AF/K1

5

(Relay output)

CHY-50AF/K1

50

(See table 1)

CHY-100AF/K1

100

CHY-200AF/K1

200

CHY-300AF/K1

300

Note: Type named, such as CHY-1AF/K1

Nominal input current: IN = 1A (AC)

Relay output state of K1: Open @ Input<1A (AC), Close @ Input≥1A (AC)

 

Table 1

K1

On-off state

K3

On-off state

Relay output

Input < IN

Open

Input < IN

Close

Input ≥ IN

Close

Input ≥ IN

Open

 

Specifications:

Input current

1…300A (AC current)

Relay output

K1 or K3 (Relay output, See table 1)

Frequency

50Hz (400Hz)

Accuracy

±1.0%

Response time

<0.35S

Supply voltage

+24V±5%

Consumption

30mA

Isolation voltage

Between primary and secondary circuit: 3KV RMS/50Hz/1min.

Operating temp.

-25…+85

Mounting on

Fastening on panel

Applications

Power supplies, industry auto-control, motor drives, electronic power system, railways etc.