  Name/Model:   Current tansformer CHG-500, CHG-1000
  Rated input Parameter:   AC 20A, 40A current / ¢9mm

SENSOR MODULE  CHG-500, CHG-1000

The SENSOR Module CHG-500, CHG-1000 is a current transformer to measure 20A…40A AC current with a

galvanic isolation between the primary and secondary circuits.

 

Current Transformer:

Type

Nominal current

Output current

Accuracy

Supply voltage

Aperture

INA

IMmA

X%

VcV

mm

CHG-500

20

40

±0.5%

No need

9

CHG-1000

40

40

±0.5%

No need

9

 

Specifications:

Principle

Transformer principle

Input current

20…40A AC current

Output current

40mA

Turns ratio

1:500 (20A, 100A), 1:1000 (40A)

Frequency

50Hz (400Hz)

Accuracy

±0.5%

Response time

<10uS

Linearity

<0.1%

Supply voltage

No need

Consumption

No need

Isolation voltage

Between primary and secondary circuit: 3KV RMS/50Hz/1min.

Operating temp.

-40…+85

Mounting on

——

Applications

Power supplies, welding machines, converters, industry auto-control, motor drives,

For industry

electronic power system, railways, rectifiers systems etc.